ModbusTCP Slave/Server - CANopen Slave

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Anybus OPC Server is supported and included with this X-gateway. It enables fast and dynamic transfer of fieldbus data to and from e.g. SCADA/HMI/Enterprice level systems based on Microsoft Windows.

The Modbus-TCP interface consists of an embedded ModbusTCP 10/100 Mbit/s 2-port Ethernet interface with IT functionality such as WEB-server, SSI-scripts, Flash file system, FTP-server, Email client, Telnet etc. It is possible to build web pages displaying and controlling a factory floor process with data from the other connected network. The EtherNet/ModbusTCP interface module is certified by the Univeristy of Michigan and has proven conformance and interoperability with leading PLC´s, HMI´s etc. The 2-port Ethernet interface will allow daisy chaining thus removes the need for any external switch.

The CANopen interface is an adapter class product allowing fast data exchange. The CANopen slave?s data map consists of Process Data Objects (fast data) and Service Data Objects (slow data). The data on the CANopen bus is updated when a change is made or on request from another node. The CANopen interface module is certified by the Can In Automation organisation and has proven conformance and interoperability with leading PLC´s, SoftPLC´s, HMI´s etc


   POINTS CLÉS
  10/100 MBit twisted pair RJ45 connection
  TCP/IP settings configurable with web-page, Configuration Tool, DHCP, ARP or with DIP switches
  Modbus/TCP class 0, class 1 and partially class 2 slave functionality
  1.4 Mbyte storage space on Flash disk
  Support for AnyBus IPconfig utility for easy TCP/IP set up
  SSI scripts used for easy display/control of process data on WEB-pages
  Gateway diagnostics via WEB-pages
  CANopen PDO and SDO data objects supported
  CANopen Unscheduled data exchange support
  CANopen profile DS-301 v.4.02
  Heatbeat and node guarding support
  Customizable PDO-mapping
  Network Stor/Restore functionality
  Support for Anybus OPC Server

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -25-65°C
Consommation:   max 400 mA
I/O Input:   Default 20 bytes, max 512 bytes
I/O Output:   Default 20 bytes, max 512 bytes
Puissance Mécanique:   IP20/Nema1
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
Modbus-TCP connector:   RJ45
Modbus-TCP address:   Any valid IP-address
CANopen baudrate:   10 kbit/s to 1 Mbit/s
CANopen connector:   D-sub 9-pin male
CANopen address:   Node address 1-99
CANopen config.:   Configured by CanOpen Master via EDS file (provided by HMS)
Modbus-TCP baudrate:   10/100 Mbit/s autodetect
Price Group:   A
Code:   AB7640