ModbusTCP Slave/Server - Profibus Slave

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Anybus OPC Server is supported and included with this X-gateway. It enables fast and dynamic transfer of fieldbus data to and from e.g. SCADA/HMI/Enterprice level systems based on Microsoft Windows.

The EtherNet interface consists of an embedded 2-port Modbus-TCP 10/100 Mbit/s interface with IT functionality such as WEB-server, SSI-scripts, Flash file system, FTP-server, Email client, Telnet etc. It is possible to build web pages displaying and controlling a factory floor process with data from the other connected network. The Modbus-TCP interface module is certified by the ODVA and has proven conformance and interoperability with leading PLC´s, HMI´s etc. The dual port Ethernet interface will allow daisy chaning and removes the need for any external switch.

The Profibus DP/DPV1 slave interface is implemented according to the standard IEC61158 as a modular slave, supporting all standard functionality such as Watchdog, Sync and Freeze and diagnostics. Including I&M functions. Standard DP as well as DPV1 acyclic data services (Class1/Class2) are supported. The Profibus interface module is certified by the Profibus user organization and has proven conformance and interoperability with leading PLC´s, HMI´s etc. Profibus address is set via rotary switches 0-99.


   POINTS CLÉS
  10/100 MBit twisted pair RJ45 connection
  TCP/IP settings configurable with web-page, Configuration Tool, DHCP, ARP or with DIP switches
  Modbus/TCP class 0, class 1 and partially class 2 slave functionality
  1.4 Mbyte storage space on Flash disk
  Support for AnyBus IPconfig utility for easy TCP/IP set up
  SSI scripts used for easy display/control of process data on WEB-pages
  Gateway diagnostics via WEB-pages
  Watchdog support
  Sync and Freeze
  Supports PA baud rate 45.45 kbit/s
  Complete Profibus DP and DPV1 (Class1/Class2) slave functionality according to IEC 61158
  Support for Anybus OPC Server

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -25-65°C
Consommation:   Max 400mA at 24VDC
I/O Input:   Max 244 bytes using DP / 512 bytes using DPV1 (max 344 bytes in+out)
I/O Output:   Max 244 bytes using DP / 512 bytes using DPV1 (max 344 bytes in+out)
Puissance Mécanique:   IP20/Nema1
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
Modbus-TCP baudrate:   10/100 Mbit/s autodetect
Modbus-TCP connector:   RJ45
Modbus-TCP address:   Any valid IP-address
Profibus baudrate:   9600 bit/s - 12 Mbit/s autodetect
Profibus address:   Node address 0-99
Profibus connector:   D-sub 9-pin female
Profibus config.:   Configured by Profibus Master via GSD file (provided by HMS)
Price Group:   A
Code:   AB7634