AS-Interface Master - ModbusTCP Slave/Server

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Anybus OPC Server is supported and included with this X-gateway. It enables fast and dynamic transfer of fieldbus data to and from e.g. SCADA/HMI/Enterprice level systems based on Microsoft Windows.

The AS-Interface Master for the Anybus X-gateway implements an extended AS-Interface master (M4), and complies to version 3.0 of the AS-I Complete Specification.
It supports up to 62 slaves with a maximum of 248 digital input and 186 output signals. It also supports 124 analog values. All standard services are available including detailed diagnostics. The network interface is optically isolated and equipped with a 2-pin pluggable screw connector. The Master supports intelligent auto-configuration via the on-board configuration button or manual configuration via a terminal program such as Hyper Terminal for Windows.
The AS-interface module is certified by the AS Interface user organization and has proven conformance and interoperability with leading manufacturers of I/O, sensors, valves etc.

The Modbus-TCP interface consists of an embedded ModbusTCP 10/100 Mbit/s 2-port Ethernet interface with IT functionality such as WEB-server, SSI-scripts, Flash file system, FTP-server, Email client, Telnet etc. It is possible to build web pages displaying and controlling a factory floor process with data from the other connected network. The EtherNet/ModbusTCP interface module is certified by the Univeristy of Michigan and has proven conformance and interoperability with leading PLC´s, HMI´s etc. The 2-port Ethernet interface will allow daisy chaining thus removes the need for any external switch.


   POINTS CLÉS
  Manages control of up to 62 AS-Interface slaves
  248 digital inputs and 186 digital outputs
  Intelligent auto configuration support
  10/100 MBit twisted pair RJ45 connection
  TCP/IP settings configurable with web-page, Configuration Tool, DHCP, ARP or with DIP switches
  Modbus/TCP class 0, class 1 and partially class 2 slave functionality
  1.4 Mbyte storage space on Flash disk
  Support for AnyBus IPconfig utility for easy TCP/IP set up
  SSI scripts used for easy display/control of process data on WEB-pages
  Gateway diagnostics via WEB-pages
  Supporting AS-Interface version 3.0
  Support for Anybus OPC Server

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -25-65°C
Consommation:   Max 400mA at 24VDC
I/O Input:   Default 20 bytes, max 64 bytes (248 digital inputs on ASI)
I/O Output:   Default 20 bytes, max 64 bytes (186 digital outputs on ASI)
Puissance Mécanique:   IP20/Nema1
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
AS-I baudrate:   167 kbit/s
AS-I connector:   2 x 2-pole 5.08 mm Phoenix pluggable screw connectors
Modbus-TCP baudrate:   10/100 Mbit/s autodetect
Modbus-TCP connector:   RJ45
Modbus-TCP address:   Any valid IP-address
Price Group:   B
Code:   AB7631