FIP Slave - Interbus Slave Cu

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The FIPIO interface is based an embedded Anybus-S module providing industrial performance and quality. FIPIO station address can be selected via switches on the end side of the module. A transformer connection on the module provides a isolated fieldbus interface.

The Interbus 2Mbit/s interface module is a slave node that can be read from/written to by an Interbus master. Interbus has two ways of exchanging data; one through fast cyclical I/O data called ?Process Data?, and one through a somewhat slower protocol called PCP, which is mainly used for configuration purposes. It supports Interbus PCP V2.0. The module supports up to 10 words of data on the bus, out of which up to four words can be used for PCP.


   POINTS CLÉS
  Supports both FIP and WorldFIP standards
  FIPIO profile FEDP (Extended Device Profile), class 0
  Transformer isolated FIP interface
  Individually isolated Bus In and Bus Out Interbus interfaces
  Up to 10 words of Process data on Interbus
  Interbus PCP v2.0 (0, 1, 2 or 4 words)

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -25-65°C
Consommation:   max 400 mA
I/O Input:   Default 20 bytes, max 64 bytes (max 20 bytes as I/O on Interbus)
I/O Output:   Default 20 bytes, max 64 bytes (max 20 bytes as I/O on Interbus)
Puissance Mécanique:   IP20/Nema1
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
FIPIO baudrate:   1 Mbit/s
FIPIO address:   Node address 0-99
FIPIO connector:   D-sub 9-pin male
Interbus Baudrate:   500Kbit/s or 2Mbit/s
Interbus connectors:   D-sub 9-pin ? Bus In male, Bus Out female
Price Group:   C
Code:   AB7874