Profibus Slave - Profibus Slave

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

Another well known name for this product functionality is DP/DP Coupler. Standard DP as well as DPV1 acyclic data services (Class1/Class2) are supported. The two Profibus interfaces are galvanically and logically isolated from each other and the two Profibus DP/DPV1 slave interfaces are implemented according to the standard IEC61158 as modular slave, supporting all standard functionality such as Watchdog, Sync and Freeze and diagnostics. Including I&M functions. The Profibus interface module is certified by the Profibus user organization and has proven conformance and interoperability with leading PLC´s, HMI´s etc. Profibus address is set via rotary switches 0-99.


   POINTS CLÉS
  Watchdog support
  Sync and Freeze
  Supports PA baud rate 45.45 kbit/s
  Galvanical isolation between two Profibus networks
  Logical isolation between the two Profibus interfaces
  Complete Profibus DP and DPV1 (Class1/Class2) slave functionality according to IEC 61158
  DP/DP Coupler functionality

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -25-65°C
Consommation:   Max 400mA at 24VDC
Baud Rate:   9600 bit/s - 12 Mbit/s autodetect
I/O Input:   Max 244 bytes using DP / 512 bytes using DPV1 (max 344 bytes in+out)
I/O Output:   Max 244 bytes using DP / 512 bytes using DPV1 (max 344 bytes in+out)
Puissance Mécanique:   IP20/Nema1
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
Profibus address ran:   Node address 0-99
Profibus connector:   D-sub 9-pin female
Profibus config.:   Configured by Profibus Master via GSD file (provided by HMS)
Price Group:   A
Code:   AB7843