Profibus Master - Modbus Plus Slave

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Anybus Profibus-DP Master interface supports connection of up to 125 slaves at baudrates up to 12 Mbit/s. The Profibus configuration is defined with NetTool-PB, the windows based configuration software for Profibus from HMS (included free of charge).
The Profibus interface module is certified by the Profibus user organization and has proven conformance and interoperability with leading manufacturers of I/O, drives, instruments etc
Configuration is downloaded to the module via the RS232 configuration port.

The Modbus Plus interface is based on licensed chip-set and software from Modicon Inc. Supporting both the Global Database and Register mapping to 3x and 4x registers this module implements a versatile Modbus Plus interface. The Modbus Plus interface module is certified by the Modconnect and has proven conformance and interoperability with leading PLC´s, HMI´s etc


   POINTS CLÉS
  Profibus configuration: NetTool-PB for Windows
  Built on Siemens ASIC ASPC2 Step E with Infineon C165 Microprocessor
  Up to 125 slaves can be connected
  Profibus configuration through RS232 configuration port
  Modbus Plus Global Data Base Transaction, Point-to-Point commands, Read holding registers, Preset single register
  Modbus Plus Host Firmware Rev. 77
  Complete Profibus DP Master according to IEC 61158

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -20-65°C
Consommation:   max 400 mA
I/O Input:   Default 20 bytes, max 512 bytes (max 64 bytes as Modbus Plus Global Data)
I/O Output:   Default 20 bytes, max 512 bytes (max 64 bytes as Modbus Plus Global Data)
Puissance Mécanique:   IP20/Nema1
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
Profibus baudrate:   9600 bit/s - 12 Mbit/s
Profibus address:   Node address 0-125
Profibus connector:   D-sub 9-pin female
Accessory order code:   018330 (NetTool-PB configuration tool for Profibus)
Modbus Plus baudrate:   1 Mbit/s
Modbus Plus address:   Node-ID and Source-ID 1-64
ModbusPlus connector:   D-sub 9-pin female
Price Group:   C
Code:   AB7809