Profibus Master - Profibus Slave

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Anybus Profibus-DP Master interface supports connection of up to 125 slaves at baudrates up to 12 Mbit/s. The Profibus configuration is defined with NetTool-PB, the windows based configuration software for Profibus from HMS (included free of charge).
The Profibus interface module is certified by the Profibus user organization and has proven conformance and interoperability with leading manufacturers of I/O, drives, instruments etc
Configuration is downloaded to the module via the RS232 configuration port.

The Profibus DP/DPV1 slave interface is implemented according to the standard IEC61158 as a modular slave, supporting all standard functionality such as Watchdog, Sync and Freeze and diagnostics. Standard DP as well as DPV1 acyclic data services (Class1/Class2) are supported. The Profibus interface module is certified by the Profibus user organization and has proven conformance and interoperability with leading PLC´s, HMI´s etc. Profibus address is set via rotary switches 0-99.


   POINTS CLÉS
  Profibus configuration: NetTool-PB for Windows
  Built on Siemens ASIC ASPC2 Step E with Infineon C165 Microprocessor
  Up to 125 slaves can be connected
  Profibus configuration through RS232 configuration port
  Watchdog support
  Sync and Freeze
  Complete Profibus DP and DPV1 (Class1/Class2) slave functionality according to IEC 61158
  Complete Profibus DP Master according to IEC 61158

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -26-65°C
Consommation:   max 400 mA at 24V
I/O Input:   Max 244 bytes using DP / 512 bytes using DPV1 (max 344 bytes in+out)
I/O Output:   Max 244 bytes using DP / 512 bytes using DPV1 (max 344 bytes in+out)
Puissance Mécanique:   IP20/Nema1
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
Profibus address ran:   Node address 0-125
Profibus connector:   D-sub 9-pin female
Accessory order code:   018330 (NetTool-PB configuration tool for Profibus)
Price Group:   B
UL File number:   E214107 UL 508 Ind Cont. Eq
Code:   AB7801