Modbus RTU Slave - CC Link Slave

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Modbus RTU Slave interface is implemented according to Modbus Protocol ref guide (PI-MBUS-300). All data is mapped to 3x and 4x Modbus areas meaning the Input Status and Output Register Word areas. The Modbus RTU standard baudrate is 19200 Bit/s but can be modified on the gateway between 1200 Bit/s to 57 600 Bit/s.

The CC-Link interface is a slave module for the CC-Link fieldbus system. It contains all the functionality needed to turn an application into a complete CC-Link remote device and it is configured to use the generic PLC profile. The CC-Link interface module is certified by the CLPA organisation and has proven conformance and interoperability with leading PLC´s, HMI´s etc


   POINTS CLÉS
  Supported Modbus RTU functions: 1, 2, 3, 4, 5, 6, 8, 15, 16, 22, 23
  Uses up to 4 occupied stations on CC-Link - configurable size
  Uses the CC-Link PLC profile for data exchange
  Modbus RTU transmission media RS485
  Support for CC-Link version 2.0 with extended data

  SPÉCIFICATIONS TECHNIQUES
Taille:   114 mm x 44 mm x 127 mm
Power Supply:   24 VDC (±20%)
Température:   -25-65°C
Consommation:   max 400 mA
I/O Input:   Default 20 bytes, CC-Link V.2: max. 368 bytes (max 896 I/O-points and 128 words) CC-Link V.1: max 48 bytes (max 128 I/O-points and 16 words)
I/O Output:   Default 20 bytes, CC-Link V.2: max. 368 bytes (max 896 I/O-points and 128 words) CC-Link V.1: max 48 bytes (max 128 I/O-points and 16 words)
Puissance Mécanique:   IP20/Nema1
UL certification:   E203225, Listed 67AM, UL-1604 Class 1, Div 2, GP A, B, C, D, Temp Code T4
ATEX certification:   ATEX 135419, II 3 G, EEx nL IIC T4, DEMKO 03
Power supply connector:   2-pole 5.08 mm Phoenix pluggable screw connector
Modbus RTU baudrate:   1200 Bit/s to 57 600 Bit/s
Modbus RTU address:   Node address 1-247
Modbus RTU connector:   D-sub 9-pin female
CC-Link baudrate:   156kbps to 10Mbps
CC-Link address:   Station 1-64
CC-Link connector:   5-pole 5.08 mm Phoenix pluggable screw connector
CC-Link config.:   Configured by CC Link Master via CSP Config file (provided by HMS)
Price Group:   A
Code:   AB7621